CODE
COMMAND
C.01
HI-LO RESET
C.02
MAX DEMAND RESET
C.03
PARTIAL ENERGY METER RESET
C.04
PARTIAL HOUR METER RESET
C.05
COUNTERS RESET
C.06
TARIFFS RESET
C.08
LIMITS RESET
C.12
TOTAL HOUR METER RESET
C.13
PARAMETERS TO DEFAULT
C.14
PARAMETERS BACKUP
C.15
PARAMETERS RESTORE
C.16
WIRING TEST
1 - Test sequence
COMMANDS MENU
– The commands menu allows executing some occasional operations like reading peaks or counters or alarms clearing, etc.
– If the Advanced level password has been entered, then the commands menu allows executing the automatic operations useful for the device configuration.
– The following table lists the functions available in the commands menu, divided by the access level required.
ACCESS LEVEL
User
Advanced
G
G
G
G
G
G
G
– Once the required command has been selected, press
executed.
– To cancel the command execution, press keys L and M simultaneously.
– To quit the commands menu simultaneously press key L and M.
WIRING TEST
– The wiring test allows to verify if the connection of the device has been executed properly.
– To be able to execute the test, the device must be connected to an active plant, with the following conditions:
• Three-phase system with all phases presence (V > 50V~ L-N)
• Current flowing in each phase > 1% of the CT primary.
• Positive flow of energies (that is a normal plant where the inductive load draws power from the supplier).
– To launch test execution, enter commands menu and select the required command per commands menu instructions.
– The test allows to verify the following points:
• Reading of the three phases
• Phase sequence
• Voltage imbalance
• Reverse polarity of each CT
• Mismatch between voltage and current phases.
– If the test does not succeed, the display shows the reason of the failure.
– If instead the test succeeds, then the condition is stored in the non-volatile memory, and a message that states the test successfully completed is shown in the
information page.
DESCRIPTION
G
Clears HI and LO peaks of all measurements
G
Clears Max Demand of all measurements
G
Clears partial Energy meters
G
Clears partial hour counter
G
Clears counters
G
Clears tariff energy meters
G
Clears limit thresholds with latch
G
Clears total hour counter
G
All setup parameters are reset to factory default value
G
Saves a backup copy of all setup parameters
G
Restores the setup parameters to backup values
G
Carries out the wiring test in order to check proper wiring of the DME. See wiring test chapter
to execute it. The device will prompt for a confirmation. Pressing
G
B
again, the command will be
2 - Test result
13