LOVATO ELECTRIC DMED310T2 Manual De Instrucciones página 8

Ocultar thumbs Ver también para DMED310T2:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1 - Active tariffe
CODE
MENU
M01
GENERAL
M02
UTILITY
M03
PASSWORD
M04
INTEGRATION
M05
HOUR METER
M06
TREND GRAPH
M07
COMMUNICATION (COMn)
M08
LIMIT THRESHOLDS (LIMn)
M09
(not implemented)
M10
COUNTERS (CNTn)
M11
ENERGY PULSING (PULn)
M12
(not implemented)
M13
INPUTS (INPn)
M14
OUTPUTS (OUTn)
M15
USER PAGE
1 - Parameter description
2 - Parameter code
8
TARIFFS
– For energy billing, the DMED310T2 can manage 4 different tariffs in addition to the total and partial energy meters.
– The tariff selection is made either by external digital inputs or optionally by means of a dedicated message on the communication protocol.
– To select among the 4 tariffs, the two input functions TAR-A and TAR-B must be used. Their binary combination selects the tariff as shown in table:
TAR-A
TAR-B
TARIFF
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
– The base module has a built-in programmable VAC input.
– The default function for this input is preset to TAR-A, thus allowing the selection between tariff 1 and 2.
– If the synchronise input for the power integration is used, then the tariff change becomes active when the sync signal triggers it; otherwise, the tariff change
takes place immediately when the status of the selecting inputs changes.
– The tariffs, each with 5 meters (active energy imported/exported, reactive imported/exported, apparent) are shown on a dedicated page, after the total-partial
energy screen.
– If the DMED310T2 is equipped with a communication port module, then it is possible to select the active tariff through the dedicated command via Modbus
protocol (see technical instruction for Modbus protocol).
PARAMETER SETTING (SETUP)
– At normal viewing, simultaneously press keys L and M to recall the main menu 1, then select
screen .
– The display will show the table below, with the parameters grouped in sub-menus with function-related criteria.
– Select the required menu with L M keys and confirm with
– To quit setup and go back to readings viewing, simultaneously press keys L and M.
– The following table lists the available sub-menus:
– Select the sub-menu and press
to show the parameters.
– Each parameter is shown with code, description and current setting value.
– To modify the setting of a parameter, select it and then press
.
DESCRIPTION
Detailed data of the installation
Language, backlight, display pages, etc.
Access codes enabling
Readings integration time
Hour counter (meter) enabling
Trend graph reading and scale
Communication ports
Limit thresholds on readings
General counters
Energy pulse count
Digital inputs
Digital outputs
User-defined page
.
2 - Viewed tariff
icon and press
to open the main menu 2 (setup)
3 - Current setting value
4 - Selected parameter
G
B