the end of the work season or more frequently if there is an
excessive build-up of soot. Excessive soot may be caused by poor
chimney draught, poor fuel quality, poor regulation of the burner, or
more or less frequent alternation of burner starts and stops.
Pay attention during operation: pulsations at start may be due to
excessive amounts of soot..
To access the heat exchanger (1), take off the rear panel (3), remove
the smoke box inspection panel (2), and then remove baffle plates
(7).
To access the combustion chamber (4) remove the burner (5).
Clean with compressed air or, if necessary, with a metal brush to
remove any deposited soot and combustion residues.
Warning
After any technical work, always check that the heater
works correctly.
7. TROUBLESHOOTING
In the event of serious anomalies, various safety devices are able to
block the machine's operation and signal the same:
• on the electrical panel
the blocking signal following intervention by the safety
L-L 230.03-BM
EN
thermostat: the reset button is located on the thermostat
F+L1+L2 box.
(for three-phase models only) the blocking signal following
intervention by the motor thermal protection: the reset
button is located inside the electrical panel.
• on the burner
the blocking signal following intervention by the burner's
flame control box.
Warning
NEVER do more than two restarts in a row: unburned fuel
can accumulate in the combustion chamber and suddenly
flare up at the next restart.
If the heater is still not working properly, please contact your
nearest dealer or authorized Service Centre.