Aspiration smoke detectors LSN improved
Setting the detector address
The Aspiration smoke detector address is set using the 8-pin DIP switches on the PC board
and a suitable sharp object. The default address is 0 (all DIP switches to off).
DIP switch settings for addresses 1 up to 127 are listed in graphic 06, page 5 , for addresses
128 up to 254 in graphic 07, page 6 .
Address
(A)
0
1 to 254
255 = CL Automatic address assignment in classic LSN
x = possible, - = not possible
Notice!
It is not permitted to use different operating modes in one loop/stub/T-tap next to each
other.
Setting the Fan Voltage
For FAS-420 systems, the standard fan voltage setting is 6.9 V.
To switch to 9 V, pull out jumper BR4.
For motherboard with jumper BR4, refer to graphic 04, page 4 .
Fan voltage
6.9 V
9 V
X = pin pair bypassed, O = pin pair open
Setting the Fan Voltage (SL Variant)
For FAS-420 systems, the standard fan voltage setting is 6.9 V.
Caution!
For SL variants, always remove jumper BR4 from the motherboard.
!
Close or open jumper the jumpers BR1 and BR2 only when the device is switched off.
Re-initialize the airflow if you have switched the fan voltage.
The fan voltage on the fan activation circuit board on SL devices is set using the jumpers BR1
and BR2. The default setting is marked in bold.
For motherboard with jumpers BR1, BR2 and BR4, refer to graphic 04, page 4 .
Fan voltage with FC‑2
6.5 V
6.9 V
9 V
Bosch Sicherheitssysteme GmbH
Operating mode
Automatic address assignment in "improved
version" LSN mode
Manual address assignment in improved version
LSN mode
mode (address range: max. 127)
Jumper BR1, pin no. 1+2
O
X
O
Quick installation guide
Network structure
Loop
X
X
X
Jumper BR4, pin no. 1+2
X
O
Jumper BR2, pin no. 1+2
X
O
O
Installation | en
21
Stub
T-tap
X
-
X
X
X
-
2020.04 | 5 | F.01U.029.274