26
en | Technical data
–
–
–
Mechanics
Displays on the device FAS-420-TP1/FAS-420-TP2
–
–
–
Displays on the device FAS-420-TT1/FAS-420-TT2
–
–
–
–
Conical duct connections for Ø 25 mm
–
–
Cable bushings
Dimensions (H x W x D)
Weight
Housing material
Housing color
Environmental conditions
Protection category as per EN 60529
Permissible temperature range
–
–
–
Permissible relative humidity (non-condensing)
Special features
Sound power level
FAS‑420‑TP1/‑TP2/‑TT1/‑TT2
Max. response sensitivity (max. light obscuration)
2020.04 | 5 | F.01U.029.274
On standby, fan voltage 9 V
On alarm, fan voltage 6.9 V
On alarm, fan voltage 9 V
Operation
Fault
Alarm
Operation
Fault
Level display
Alarm
Aspiration pipe
Air-return pipe
Aspiration smoke detector
PVC pipe system
ABS pipe system
Quick installation guide
Aspiration smoke detectors LSN improved
285/290 mA
325/330 mA
210/230 mA
245/280 mA
285/305 mA
325/360 mA
Green LED
Yellow LED
1 red LED/2 red LEDs
Green LED
Yellow LEDs
1 x / 2 x smoke level display, each
with 10 segments (1-10)
1 x 3 / 2 x 3 red LEDs for info alarm,
internal alarm and main alarm
1 pipe/2 pipes
1 pipe
5 x M 20 and 2 x M 25
292 x 200 x 113 mm
Approx. 1.5 kg
Plastic (ABS)
Papyrus white (RAL 9018)
IP 20
-20 °C to +60 °C
0 °C to +60 °C
-40 °C to +80 °C
10 to 95%
45 dB(A)
Bosch Sicherheitssysteme GmbH