8.2.1 Certifying the configuration
Please certify the configuration of the inverter in accordance with the current HOPPECKE parame-
ter with your signature. The original of the signed document must remain with the operator of the
PV system and kept in safe custody.
Date ________________________________
____________________________________
Installation/Solar Engineer
9 Maintenance
Regular care and maintenance of your battery system is essential for ensuring the required reli-
ability and long service life.
The batteries must be maintained every two years, by a suitable specialist in the course of
designated use.
Maintenance:
Measurements to be carried out; the measurements must be documented and the records must
be stored (see Appendix 11.2):
1. Measurement of the room temperature (the room temperature must be between 10 °C and
30 °C).
2. Measurement of the surface temperature of each individual block. There should be a maximum
deviation of 5 K between the individual temperatures.
In the event of deviations in the measurements listed above, please contact the HOPPECKE
Service department or an authorised partner company.
Tests:
3. Visual inspection of the battery carrier and the batteries (clean batteries and carrier if required;
observe safety instructions).
4. Visual inspection of the PVC piping of the central degasification system and condensate
separator.
Recording of measurements and tests (including measured values).
If during maintenance, relevant quantities of acid (container is more than half filled) become appa-
rent in the condensate separator, please contact the HOPPECKE Service department.
10 Fault Rectification
If faults are identified on the battery or the charger equipment, contact the HOPPECKE Service
department or an authorised partner company promptly.
Installation and Operating Manual sun | powerpack
7140803000 V1.1 (10.2015)
46
____________________________________
Operator/End customer
classic
11 Appendix
11.1 Appendix 1 - Open-circuit voltages and identification of the battery blocks
Identification number
Battery block 1
Battery block 2
Battery block 3
Battery block 4
Battery block 5
Battery block 6
Battery block 7
Battery block 8
Battery block 9
Battery block 10
Battery block 11
Battery block 12
Battery block 13
Battery block 14
Battery block 15
Battery block 16
1. Recharging during storage done on: _______________________________________________________________
Battery charger used (Manufacturer and type): ________________________________________________________
Company: _____________________________________
Signature: ______________________________________
2. Recharging during storage done on: _______________________________________________________________
Battery charger used (Manufacturer and type): ________________________________________________________
Company: _____________________________________
Signature: ______________________________________
Installation and Operating Manual sun | powerpack
Commissioning date
Open-circuit voltage in V
Name: _________________________________________
Name: _________________________________________
classic
7140803000 V1.1 (10.2015)
47