Modbus Address
Hex
Decimal
754C - 754C 30029 - 30029 Limit #1 Out High Setpoint
754D - 754D 30030 - 30030 Limit #1 In High Threshold
754E - 754E 30031 - 30031 Limit #1 Out Low Setpoint
754F - 754F
30032 - 30032 Limit #1 In Low Threshold
7550 - 7554
30033 - 30037 Limit #2
7555 - 7559
30038 - 30042 Limit #3
755A - 755E 30043 - 30047 Limit #4
755F - 7563
30048 - 30052 Limit #5
7564 - 7568
30053 - 30057 Limit #6
7569 - 756D 30058 - 30062 Limit #7
756E - 7572
30063 - 30067 Limit #8
12-Bit Block
9C40 - 9C40 40001 - 40001 System Sanity Indicator
9C41 - 9C41 40002 - 40002 Volts A-N
9C42 - 9C42 40003 - 40003 Volts B-N
9C43 - 9C43 40004 - 40004 Volts C-N
9C44 - 9C44 40005 - 40005 Amps A
9C45 - 9C45 40006 - 40006 Amps B
9C46 - 9C46 40007 - 40007 Amps C
9C47 - 9C47 40008 - 40008 Watts, 3-Ph total
9C48 - 9C48 40009 - 40009 VARs, 3-Ph total
9C49 - 9C49 40010 - 40010 VAs, 3-Ph total
9C4A - 9C4A 40011 - 40011 Power Factor, 3-Ph total
9C4B - 9C4B 40012 - 40012 Frequency
9C4C - 9C4C 40013 - 40013 Volts A-B
9C4D - 9C4D 40014 - 40014 Volts B-C
e
Electro Industries/GaugeTech
1
Description
Format
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
12-Bit Readings Section
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
Doc# ES145721
Units or
6
Range
Resolution
-200.0 to +200.0
0.1% of full scale
-200.0 to +200.0
0.1% of full scale
-200.0 to +200.0
0.1% of full scale
-200.0 to +200.0
0.1% of full scale
same as Limit #1
same as Limit #1
0 or 1
none
2047 to 4095
volts
2047 to 4095
volts
2047 to 4095
volts
0 to 4095
amps
0 to 4095
amps
0 to 4095
amps
0 to 4095
watts
0 to 4095
VARs
2047 to 4095
VAs
1047 to 3047
none
0 to 2730
Hz
2047 to 4095
volts
2047 to 4095
volts
Comments
Setpoint for the "above" limit (LM1), see
notes 11-12.
Threshold at which "above" limit clears;
normally less than or equal to the "above"
setpoint; see notes 11-12.
Setpoint for the "below" limit (LM2), see
notes 11-12.
Threshold at which "below" limit clears;
normally greater than or equal to the "below
setpoint; see notes 11-12.
same as Limit #1
Block Size:
read-only except as noted
0 indicates proper meter operatio
2047= 0, 4095= +150
volts = 150 * (register - 2047) / 2047
0= -10, 2047= 0, 4095= +10
amps = 10 * (register - 2047) / 2047
0= -3000, 2047= 0, 4095= +3000
watts, VARs, VAs =
3000 * (register - 2047) / 2047
1047= -1, 2047= 0, 3047= +1
pf = (register - 2047) / 1000
0= 45 or less, 2047= 60, 2730= 65 or more
freq = 45 + ((register / 4095) * 30)
2047= 0, 4095= +300
volts = 300 * (register - 2047) / 2047
MM-7
#