Mitsubishi Electric PUMY-P48NKMU1-BS Manual De Instalación página 5

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Fig. 2-5
Fig. 2-9
Fig. 2-12
Fig. 2-15
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
Refer to the gures for each case.
1 Obstacles at rear (Fig. 2-5)
2 Obstacles at rear and above (Fig. 2-6)
3 Obstacles at rear and sides (Fig. 2-7)
4 Obstacles at front (Fig. 2-8)
* When using the optional air outlet guides, the clearance is 19-11/16" (500 mm) or more.
5 Obstacles at front and rear (Fig. 2-9)
* When using the optional air outlet guides, the clearance is 19-11/16" (500 mm) or more.
6 Obstacles at rear, sides, and above (Fig. 2-10)
Do not install the optional air outlet guides for upward air ow.
Fig. 2-6
Fig. 2-10
Fig. 2-13
Fig. 2-16
Leave 1" (25 mm) space or more between the units.
1 Obstacles at rear (Fig. 2-11)
2 Obstacles at rear and above (Fig. 2-12)
3 Obstacles at front (Fig. 2-13)
4 Obstacles at front and rear (Fig. 2-14)
5 Single parallel unit arrangement (Fig. 2-15)
6 Multiple parallel unit arrangement (Fig. 2-16)
7 Stacked unit arrangement (Fig. 2-17)
Fig. 2-7
o more than 3 units must be installed side by side. In addition, leave space as shown.
Do not install the optional air outlet guides for upward air ow.
* When using the optional air outlet guides, the clearance is 39-3/8" (1000 mm) or more.
* When using the optional air outlet guides, the clearance is 39-3/8" (1000 mm) or more.
* When using the optional air outlet guides installed for upward air ow, the clearance is 39-3/8"
(1000 mm) or more.
* When using the optional air outlet guides installed for upward air ow, the clearance is 59-1/16"
(1500 mm) or more.
The units can be stacked up to 2 units high.
o more than 2 stacked units must be installed side by side. In addition, leave space as
shown.
(inch)
Fig. 2-8
Fig. 2-11
Fig. 2-14
Fig. 2-17
5

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pumy-p36nkmu1-bs

Tabla de contenido