Field settings table
Temperature values displayed on the digital controller (user interface) are in °C.
Temperature values in °C are between brackets. Conversion from °C to °F is for information only.
First
Second
code
code
Setting name
0
User permission level
00
User permission level
1
Weather dependent set point
00
Low ambient temperature (Lo_A)
01
High ambient temperature (Hi_A)
02
Set point at low ambient temperature (Lo_TI)
03
Set point at high ambient temperature (Hi_TI)
2
Disinfection function
00
Operation interval
01
Status
02
Start time
03
Set point
04
Interval
3
Auto restart
00
Status
4
Space heating off temperature
00
Installation related setting
01
Installation related setting
02
Space heating off temperature
03
Installation related setting
04
Installation related setting
5
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
6
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
7
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
8
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56183-1
Installer setting at variance with default value
Date
Value
Date
Default
Value
value
Range
3
2/3
14
–4~41
(–10)
(–20~5)
59
50~68
(15)
(10~20)
104
77~131
(40)
(25~55)
77
77~131
(25)
(25~55)
Mon~Sun,
Fri
All
1 (ON)
0/1
23:00
0:00~23:00
158
104~176
(70)
(40~80)
10
5~60
0 (ON)
0/1
95
57.2~95
(35)
(14~35)
Step
Unit
1
—
1.8
°F
(1)
(°C)
1.8
°F
(1)
(°C)
1.8
°F
(1)
(°C)
1.8
°F
(1)
(°C)
—
—
—
—
1:00
hour
9
°F
(5)
(°C)
5
min
—
—
1.8
°F
(1)
(°C)
Operation manual
14