Wiring the device
6
Important notes
Proceed as follows to disconnect the internal connection between the filters and PE:
94GG67IT67
Fig. 6−1
1. Find the metal strap on the left of the device.
2. Unbolt the screws to remove the metal strap.
3. Unbolt the screw at position "IT" and insert the metal strap.
4. Tighten all screws.
– Tightening torque: 3.4 Nm (30 lb−in)
After this, the device is suitable for operation in IT systems.