Lamborghini Caloreclima EM 12-E Manual Para La Instalacion Y El Mantenimento página 38

Quemadores de gas con una llama para calderas normales/presurizadas
Ocultar thumbs Ver también para EM 12-E:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EM 18/2-E
Legend
1 Control box
2 7 Poles connector
4 Valve gas
5 Anti-interference filter
6 Ignition transformer
7 Fuse
8 Main switch
9 Gear motor for air shutter opening
10 Remote lock-out warning light
WARNING:
- Do not invert the neutral with the phase.
- Make the connection to an effi cient earthing system.
- The electrical power line to the burner must be fi tted with an omnipolar switch with an ope-
ning of at least 3 mm between the contacts.
- The earth connection to the terminal board of the burner must be made with a cable at least
20 mm longer than the phase and neutral cables.
- Must be workmanlike performed and comply with the regulations in force.
NOTE: Always make sure that no more than two wires are connected to each terminal.
UK
38
11 Temperature boiler thermostat
13 Burner motor
14 Air pressure switch
15 Min. gas pressure switch
16 Control electrode
17 Room thermostat
18 Boiler thermostat

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Em 12l-eEm 18-eEm 18l-eEm 18/2-e

Tabla de contenido