Pressure Switch - Lamborghini Caloreclima EM 12-E Manual Para La Instalacion Y El Mantenimento

Quemadores de gas con una llama para calderas normales/presurizadas
Ocultar thumbs Ver también para EM 12-E:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there
be a drop in combustion air pressure.
It will be calibrated at a pressure below 1st stage rated-flow on-burner air pressure,
checking that CO values do not exceed 10,000 p.p.m...
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up
or to shut it down if the gas pressure falls below the minimum required level. This set-
ting should be 40% lower than the gas pressure obtained with the burner operating at
maximum delivery..

PRESSURE SWITCH

Type:
LGW 3 A2
LGW 10 A2
GW 50 A5
GW 150 A5
Remove the cover and adjust
dial A
mODELLO
EM 12-E / EM12L-E
EM 18-E / EM18L-E
EM 18/2-E
CHECKING CONTROL BOX IONIZATION CURRENT
The minimum value of 3 μA should be observed, and large oscillations are to be avoi-
ded.
Microampermeter
Pressure
connector
aiR
SETTING
PRESSURE
RANGE
SWiTCH
mbar
LGW 3 A2
0,4-3,0
LGW 10 A2
1-10
LGW 10 A2
1-10
GaS
SETTING
PRESSURE
RANGE
SWiTCH
mbar
GW 50 A5
5-50
GW 150 A5
5-150
UK
45

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Em 12l-eEm 18-eEm 18l-eEm 18/2-e

Tabla de contenido