9-14. Table of Self-Diagnostic Functions and Corrections

Wired remote
controller
Indoor unit
display
receiver lamp
1:1 connection (Single type)
(Field supply)
Nothing is
Nothing is
• Indoor operation switch is OFF.
displayed
displayed
• Indoor unit power is not ON.
• Automatic address setting has not been
completed.
E01 displayed
• Inter-unit control wiring is cut or is not
connected correctly.
Operating lamp
is blinking.
E14 displayed
——————
• Indoor-outdoor inter-unit wiring is not
E04 displayed
connected correctly.
E06 displayed
——————
Standby lamp is
blinking.
• Indoor unit capacity is too low.
E15 displayed
• Indoor unit capacity is too high.
E16 displayed
Operation lamp
• Reversed phase in the outdoor unit
and Standby
single-phase or open phase in the
P05 displayed
lamp are blinking
outdoor unit 3-phase power.
alternately.
L02 displayed
• Indoor-outdoor unit type mismatch.
• Indoor-outdoor units are not setting
L13 displayed
correctly.
Both the
Operation lamp
L04 displayed
——————
and Standby
lamp are blinking
together.
L07 displayed
——————
Operation lamp
• No gas
and Standby
P15 displayed
lamp are blinking
alternately.
Cause
Group connection
Correction
(Simultaneous multi
system)
• Same at left.
• Set the indoor operation switch ON.
• Turn ON the indoor unit power.
• Same at left.
• Check the inter-unit control wiring.
• Perform automatic address setting
(See 9-15).
• Remote controller
• Check the remote controller crossover
crossover wiring is cut
wiring.
or is not connected
• Perform automatic address setting again.
correctly.
• Same at left.
• Connect the wiring correctly.
• Inter-unit control
• Refer to 9-15 System Control, and make
wiring is cut or is not
the correct settings.
connected correctly.
• Same at left.
• Check that the total capacities of the indoor
and outdoor units are appropriate.
• Same at left.
• Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
• Same at left.
• Connect the units correctly.
• Same at left.
• Connect the units correctly.
• Same at left.
• Connect the units correctly.
• Outdoor unit address is
• Connect the units correctly.
duplicated.
• Remote controller
• Perform automatic address setting
crossover wiring is
(See 9-15).
connected to the indoor
unit, however, it is set
for individual operation.
• Same at left.
• Check the refrigerant cycle (for gas leaks).
29
2011/02/23 13:37:54
Big_PAC_eng.indb 28

9-15. System Control

System control refers to the link wiring connection for control of
simultaneous-operation multi systems, group control, and main-
sub remote controller control.
9-15-1. Basic wiring diagram 1
Single type
● Be careful to avoid miswiring when connecting the wires.
(Miswiring will damage the units.)
(for 3-phase outdoor unit)
Example: Using a wireless remote controller with a system
Ground
System address (S2)
(Setting at shipment: "0")
Leakage breaker
Outdoor unit
L1
L2
L3
N
1 2
(Using a wired remote controller with a
single-type system)
Inter-unit control wiring
1. To connect the remote controller, a
Leakage breaker
L
N
Indoor
1
unit
2
No. 1
Ground
2P
Out-
(white)
door
Wireless remote
unit
controller
Ground
(Wiring procedure)
(1) Connect the crossover wiring to 1 and 2 on the remote
controller wiring terminal plate for units.
(2) Connect the inter-unit control wiring to 1 and 2 on the No.
1 indoor unit terminal plate, and to 1 and 2 on the outdoor
unit terminal plate.
Also connect the inter-unit control wiring between the
indoor units.
(3) When the indoor and outdoor unit power is turned ON,
automatic address setting is performed (when there is only
1 outdoor unit or when the system address is "0").
NOTE
* If the system address is "0", automatic address setting is
performed when the power is turned ON (in the case shown in
Basic wiring diagram 1).
This requires approximately 4 – 5 minutes (when the outdoor /
indoor unit ratio is 1:1 as shown in Basic wiring diagram 1).
During automatic address setting, LED 1 and 2 on the outdoor
unit control PCB blink alternately. These LED turn OFF when
automatic address setting is completed.
remote controller cord is required.
Leakage breaker
Leakage breaker
4P
terminal
L1
plate
Ground
L2
L
L3
N
Indoor
1
N
unit
2
1
2
Wired remote
controller
(Field
supply)
1 2
white black
Fig. 9-10
30
2011/02/23 13:37:54