FAILSAFE model
Actuator with failsafe integrated security system (ON/OFF mode compulsory)
Failsafe model integrate a battery pack monitored by an electronic board inside the actuator. Its function is to relay in
case of power supply failure on terminal PIN 1,2 and 3 of the actuator. The failsafe system can be set on different posi-
tion like normally open (NO) or normally closed (NC). It depends on customer application.
The electronic board monitors the battery pack and check the status of battery (cycle load and failure)
If a battery failure is detected , a contact on PIN 65 and 66 switch off. If customer use this contact he could be aware
that there is a failure on battery in the actuator without remove cover and plan the replacement.
Fail safe option required ON/OFF mode.
Loading electronic board
Voltage
Nominal current
Courant maximal
Initial loading time
Load state feedback relay
Temperature
LED meaning
LED
DSBA3200 • Rév. 15/02/2018
D
B
C
18V DC
0,8A
2,4A
14h max
24V DC - 1A max
-10°C to 40°C
Green LED
Red LED
Off
Blinks/off/Blinks... Battery disconnected or out of service
On
Blinks
On
Off
Blinks rapidly
Off
Off
Blinks rapidly
E
REP
DESIGNATION
A
18V DC terminal strip
B
Block battery terminal strip
C
State feedback terminal strip (load or battery failure)
D
Green LED
E
Red LED
Battery loading cycle in progress (max 14h)
Battery loading cycle finished
Actuator electrical supply during 3 minutes (failure mode)
Microcontroller failure