Electronic Boards - VALPES ER PLUS Serie Manual De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Electronic boards

15V-30V 50/60Hz (12V-48V DC)
A
G
B
C
15V-30V 50/60Hz (12V-48V DC)
A
C
REP
DESIGNATION
A
Earth screw
B
Power supply and control terminal
*C*
Protection fuses
D
LED 2 : microprocessor ok
* Fuses for multivolt boards
- SNAA720100 board: 2A / T 250V (Multicomp MST 2A 250V)
- SNAA720000 board: 500mA / T 250V (Multicomp MST500MA 250V)
- SNAA730100 board: 5A / T 125V (Littelfuse 39615000000)
- SNAA730000 board: 3,15A / T 250V (Multicomp MST 3,15A 250V)
** Possible defects : limitation of current, thermic limitation or program error
=> check that the valve torque is not superior to the maximum torque stand by the actuator
=> check that the actuator do not exceed the duty cycle indicated (possible overheat)
To re-start the actuator, reverse the sense of rotation or switch the power off and on.
22
SNAA720100
F
D
SNAA730100
B
G
C
100V-240V 50/60Hz (100V-350V DC)
E
G
A
B
C
100V-240V 50/60Hz (100V-350V DC)
F
E
D
A
REP
DESIGNATION
E**
LED 3 : detected failure
F
LED 1 : power supply presence
G
Failure report terminal strip (24V DC - 3A max)
UK
SNAA720000
F
D
SNAA730000
B
C
C
DSBA3200 • Rév. 15/02/2018
ENGLISH
E
F
E
D
G

Publicidad