Electric Lock Early Release Before The Gate Moves; Electric Lock Time; Parameter 28); "Generator Set" Mode - Roger H70/200AC Instrucciones Y Advertencias Para El Instalador

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 68
28 01

Electric lock early release before the gate moves

00
02
SECONDS
-
29 03
Electric lock time (release time that is added on to the early lock release, parameter
00
DISABLED
01
06
SECONDS
-
If the opening jolt feature is enabled (par.
30 00

"Generator set" mode

00
OFF
01
ON (Additional digital filtering for power from generator sets)
Enabling this function improves movement control when the system is powered by generator sets.
31 06

Torque level during normal travel

01
08
1 minimum torque... 8 maximum torque
-
9-
NOTE: parameter
This parameter is always less than or equal to parameter
32 06

Torque level during slowed travel

01
08
1 minimum torque... 8 maximum torque
-
33 08

Starting torque level

01
08
1 minimum torque... 8 maximum torque
-
34 02

Soft-start ramp setting

00
OFF (soft start disabled)
01
02
soft start
-
03
04
even softer start (only available if encoder is enabled)
-
01
A low value (
) means rapid acceleration, while a high value (
slowly so that the leaf starts moving more smoothly and gradually.
If the encoder is disabled (
NOTE: avoid setting the value
35 08

Starting torque level for reversing triggered by safety edge or encoder

00
OFF (starting torque disabled: implements the torque set via parameter
01
08
1 minimum torque... 8 maximum torque
-
36 03

Starting torque time

00
20
how long, in SECONDS, the motors run with the set starting torque (parameter
-
Starting torque controls motor power when movement is starting, providing the maximum torque to
ensure the leaf starts moving; depending on operating conditions, it may be worth increasing this time - for
instance, if the system is installed in a rigid climate where the structure is in danger of freezing and might
struggle to start moving. It is implemented immediately after the soft-start.
38
in easy setup mode.
75  00
), the factory default setting is
04
when dealing with a particularly heavy gate.
29
), then par.
must have a higher value than par.
33
.
04
02
) brings the motors up to full speed more
.
28
)
38
.
31
)
33
)
37

Publicidad

Tabla de contenido
loading

Productos relacionados para Roger H70/200AC

Tabla de contenido