Honeywell Home HE360 Manual De Instrucciones página 12

Humidificador y kit de instalación
Ocultar thumbs Ver también para HE360:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

HE360 HUMIDIFIER AND INSTALLATION KIT
WIRING
CAUTION
Hazardous Voltage.
Can cause personal injury or equipment damage.
Disconnect power supply before installing or servicing equipment.
IMPORTANT
— Use THIS wiring diagram—NOT the one supplied with humidistat instructions.
— All wiring must comply with applicable local code, ordinances and regulations.
Wire the humidifier solenoid valve, pressure switch and humidistat. See Fig. 12.
NOTE: It is acceptable to switch the position of the red and white wires when wiring the equipment.
1. Run the two-strand thermostat wire from the humidifier to the humidistat, and from the humidistat to the
pressure switch.
2. Cut two (2) lengths of thermostat wire to reach between components, leaving adequate wire at both ends
for connections.
NOTE: Humidistat and pressure switch can be wired in any order.
3. At the humidifier, use one length of thermostat wire to connect a red wire to one of the yellow humidifier
wires and a white wire to the remaining yellow humidifier wire. (The red wires from the humidifier are not
used.)
4. At the pressure switch, use the remaining length of thermostat wire to connect a red wire to the C terminal
and a white wire to the NO terminal using spade connectors and pliers. (The NC terminal is not used.)
5. Connect the white wires from each length of thermostat wire to each of the black wires of the humidistat
using wire nuts.
6. Connect the remaining red wires together using a wire nut.
69-2631ES—07
HUMIDIFIER
YELLOW
YELLOW
WHITE
RED
WHITE
Fig. 12. Wiring the controls.
AIR PRESSURE
HUMIDISTAT
BLACK
BLACK
WHITE RED
WHITE
RED
RED
12
SWITCH
M34590A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

He360a1075

Tabla de contenido