Honeywell Home HE360 Manual De Instrucciones página 4

Humidificador y kit de instalación
Ocultar thumbs Ver también para HE360:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

HE360 HUMIDIFIER AND INSTALLATION KIT
Determining Best Location for Humidifier
CAUTION
Temperature and Static Pressure Hazard.
Can cause property or equipment damage.
Locate humidifier where ambient temperature is between 32°F (0°C) and 160°F (71°C).
Do not install humidifier where freezing temperatures could occur.
Be sure supply plenum static pressure is no greater than 0.4 in. wc and water pressure is no greater than
124 psi.
• Select a location for the humidifier on the supply (warm air stream) plenum. See Fig. 1.
• Select a location that cannot damage the air conditioner A-coil during installation.
• Do not locate the humidifier on the furnace body.
• Allow adequate clearance in front of and above the humidifier so you can easily remove the cover to perform
routine maintenance.
Mount the humidifier at least 3 in. (78 mm) above the furnace body to allow adequate space for the sole-
noid valve and drain line.
Mount the humidifier in a conditioned space to prevent freezing.
R E
Selecting Water Supply Location
• Use either hard or soft water in the humidifier and either hot or cold water. The water flow rate, with the
humidifier running, is 3.5 gal/hr (13 liters/hr) to flush the pad and provide moisture for evaporation.
• Make sure that the 20 ft (6.2m) of feed water tubing provided is adequate to connect the water supply (saddle
valve) with the humidifier solenoid valve.
69-2631ES—07
H O
R N
T U
R N
T U
R E
W B
L O
Fig. 1. Typical humidifier installation locations.
T A L
O N
R I Z
R N
T U
R E
W N
D O
O
F L
O Y
4
R N
T U
R E
O Y
H B
H I G
M12808A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

He360a1075

Tabla de contenido