Descargar Imprimir esta página

LOVATO ELECTRIC GEX69C Serie Manual De Instrucciones página 14

Ocultar thumbs Ver también para GEX69C Serie:

Publicidad

GB
Annex 5: EMC table (electromagnetic compatibility)
Test
Electrostatic discharges
Electromagnetic H.F. field
Fast transients (Burst)
Fast transient (surge discharge)
Conducted disturbances
Electromagnetic field, industrial frequency
Voltage dips, interruptions and voltage variations
Test
Emission of harmonic current
Unwanted voltage
Radiated emission
NOTE: The installation of this device in a domestic environment can cause radiofrequency interference
EN 61000 is equivalent to IEC 61000 - EN 55011 is equivalent to CISPR11
CRITERION A: Normal service behaviour in determined limits
CRITERION B: Transient alteration of the service. The appliance gets back to the normal performing without the intervention of the operator
CRITERION C: A loss of function is allowed, provided the function is self-recoverable, or can be restored by the operation of the controls or cycling of the power to the EUT by the user in
accordance with the manufacturer's instructions.
Test level 3: Typical industrial environment, without special installation measures
Test level 4: Severe industrial environment
Special level: Level of higher electromagnetic severe environment
14
Inmunity
Standard
According to standard According to standard Results achieved
UNE/EN 61000
EN 61000-4-2
Special, B
EN 61000-4-3
Level 3, A
EN 61000-4-4
Level 3, B
EN 61000-4-5
Level 3, B
EN 61000-4-6
Level 3, A
EN 61000-4-8
Level 4, A
EN 61000-4-11
Criterion B
Criterion C
Criterion C
Emission
Standard
According to standard According to standard Results achieved
UNE/EN 61000
EN 61000-3-2
Level 3
Level 3
EN 55011
Level 3
N 55011
Level 3
IEC 60947-6
Special, A
Special, A
±4KV equipment discharge
Level 3, A
Level 3, A
10V/m. from 80MHz to 1 GHz
Level 3, A
Level 4, A
Level 3, A
Special, A
±4KV power supply L1-L2
Generator impedance 2Ω
Level 3, A
Level 3, A
––
Level 4, A
––
Criterion A
––
Criterion A
––
Criterion B
IEC 60947-6
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
Values achieved
in tests
±8KV air discharge
±4KV power supply,
freq. Rep. 2,5kHz
±2KV signal supply,
freq. Rep 5kHz
(wave 1.2/50 ms)
10V supply and signal
Field intensity 30A/m
30% Un - 1000 ms
60% Un - 1000 ms
95% Un - 5000 ms
Values achieved
in tests
0,02A total current
(manual mode)
0,04A total current
(automatic mode)
Qualified
Qualified