RBCTWP30E.book Page 7 Thursday, June 24, 2004 5:39 PM
Wiring Diagram
Remote Controller
Main Indoor unit
A
1
1
Outdoor Unit
L
Power supply
Wiring Specification
Specification of Wires Between Units and Numbers of Wires.
Outdoor unit - indoor unit
(main unit)
Indoor unit
- indoor unit
(main unit)
(sub unit)
Remote control wiring
Grounding wire of indoor sub unit
Procure necessary parts and perform all connection work locally.
NOTES
When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power
was on. However, it is not a trouble.
Automatic address
While automatic addressing, the operation can not be performed on the remote controller.
For automatic addressing, Max. 10 minutes (generally, approx. 5 minutes) are required.
When power will be turned on after finish of automatic addressing;
It will require Max. 10 minutes (generally, approx. 3 minutes) that outdoor unit starts operation after power was on.
Sub Indoor
B
Unit
2
3
3
2
N
No. of wires
Wire diameter
No. of wires
Wire diameter
No. of wires
Wire diameter
Between 0.5mm
7
A
B
1
2
3
4 (Include ground wire)
2
H07RN-F or 245IEC66 1.5mm
or more
2
2
H07RN-F or 245IEC66 1.5mm
or more
2
2
2
and 2mm
(up to 200m)
2
H07RN-F or 245IEC66 1.5mm
or more