7. LOADING OF THE FACTORY SETTINGS

In order to load the factory settings in the SRW 01, one must follow
the steps below:
1 - Switch off the SRW 01;
2 - Switch on the SRW 01 with the RESET button pressed, keep it for
10 seconds. This procedure deletes the user Ladder program.
NOTE!
The factory settings can also be loaded by setting
parameter P204 = 5 and cycling the SRW 01 power
subsequently. This procedure maintains the user Ladder
program.

8. DIAGNOSIS

The error, alarm and fault diagnosis can be achieved through the three
status LEDs of the SRW 01 or by means of HMI messages.

9. DIAGNOSIS VIA LEDs

Table 1: SRW 01 status via LEDs
LED
STATUS
Flashing green
Flashing red
NET
TRIP
Flashing green
Flashing red
Signaling
Green
The relay is suitable for use
Fault - does not switch off the motor
Error - switches off the motor
According to each protocol communication manual
Green
Normal motor
Alarm - does not switch off the motor
Trip - switches off the motor
Description
11