The LMRC-111-16M room controller can be mounted external to any junction box with 1/2" knockouts, placing it in the plenum space.
The relay is rated for up to 16A. Do not connect different load types to the same relay. The Line (Black) and Load (Red) wires are #14
AWG. The Neutral (White) wire is #18 AWG.
For dimming ballasts, either or both the Class 1 and Class 2 0–10V wires may be connected. For Class 1 Dimming, wiring is #18 AWG.
Connect the 0–10V control wires to the 0–10V terminals that match the load relay output connection.
Class 1 is preferred in new installations when the violet and grey dimming signal wires are included in the fixture power cable. Class 2 is
used for new or existing installation when it is easier to run the violet and grey dimming signal wires outside the fixture cable.
Class 1 and Class 2 wiring should be maintained thoughout the installation and cannot be swapped—appropriate wiring practices
should be used. Class 1 and Class 2 circuitry in the LMRC units are galvanically isolated.
The LMRC-111-16M communicates to all other DLM devices connected to the DLM Local Network. Connections shown are for example
only. The low voltage LMRJ cables can connect to any DLM device with an open RJ45 receptacle.
LMRC-111-16M with Class 1 Dimming
Corner Mount
Ceiling Mount
Sensor
Sensor
Scene Switch
0–10V Class 2 Connections
Tie-Down for
0-10V & LMRJ
cables
WARNING: TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
MOUNTING, WIRING, AND CONNECTING
TO A DLM NETWORK
Line
DLM Local Network
Voltage
Low Voltage
LMRJ Cables
Black wire
White wire
Room
Controller
Deep J-Box
Red wire to Load 0-10V Class 1 Gray and Violet wires to Load
Gray (-)
Violet (+)
Line/Hot
Neutral
Load
Switched with
0-10 Volt control
Dimming Ballast
LED Driver, etc.
Daylighting
Sensor
2
LMRC-111-16M with Class 2 Dimming
Line
Voltage
Black wire
White wire
Room
Controller
Deep J-Box
Class 1 0-10V Gray and Violet wires
Red wire to Load
(capped off)
0-10V Class 2 Dimming control wires
PLACEMENT EXAMPLE
Corner Mount
Occupancy
Sensor
LMRC-111-16M
Room Controller
J Box
Ceiling Mount
Occupancy
To
Sensor
Load
Class 2 to 0-10V
Dimming Ballast
Line/Hot
Neutral
Load
Switched with
0-10 Volt control
Dimming Ballast
LED Driver, etc.
DLM Local Network
(low voltage, Class 2)
LMRJ cables
Switch/
Dimmer