Features
The SMART3000RMOD2U UPS System features a hot-swappable power module. When the bracket holding the power module in place is removed (there
is no manual bypass switch on the unit), the UPS automatically switches to "BYPASS" mode. This allows the power module to be removed for
maintenance, repair or replacement without disrupting power to connected loads. Review the location and function of the UPS system's features before
installing and operating it.

Front Control Panel

1
"Load/Battery" Bar Graph: This display indicates the power load and battery levels.
2
"On" Button: Press this button and hold it for one second until you hear a beep to turn the UPS System ON. If the battery alarm is sounding, press
this button to silence it.
3
"Off/Standby" Button: Press this button and hold it for one second to turn the UPS system OFF.
4
"Load Level" LED (Green): This LED illuminates when the Load/Battery Bar Graph is displaying the load level.
5
"Battery Capacity" LED (Green): This LED illuminates when the Load/Battery Bar Graph is displaying the battery capacity.
6
"AC Mode" LED (Green): This LED illuminates when the UPS System is ON and supplying connected equipment with AC power from a utility
source.
7
"Automatic Voltage Regulation (AVR) Mode" LED (Yellow): This LED illuminates whenever the UPS system is lowering voltage and blinks
continuously when the UPS is boosting voltage.
8
"Overload" LED (Red): When this LED is illuminated, the load is >105%. Clear the overload immediately by unplugging some of your equipment
from the outlets until the LED changes from red to yellow (or green). CAUTION! Any overload that is not immediately corrected by the user
may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.
9
"UPS Fault" LED (Red): This LED illuminates if the UPS system has an internal fault.
10
"Site Wiring Fault" LED (Red): This LED illuminates if the UPS system detects a site wiring problem.
11
"Battery Fault" LED (Yellow): This LED illuminates if the UPS system senses a weak, bad or disconnected battery.
12
"On Battery" LED (Green): This LED illuminates if the UPS system is operating from battery power.