Quick Installation

Plug the UPS into an outlet on a dedicated
1
circuit.
NOTE: After you plug the UPS into a live AC outlet, the UPS
will automatically charge its batteries* and will supply
power to its outlets unless the unit is turned OFF (see Step 3
below).
Plug your equipment into the UPS.*
2
* Your UPS is designed to support only electronic equipment. You will overload
the UPS if the total VA ratings for all the equipment you connect exceeds the UPS's
Output Capacity. To find your equipment's VA ratings, look on their nameplates.
If the equipment is listed in amps, multiply the number of amps by 120 to
determine VA. (Example: 1 amp × 120 = 120 VA). If you are unsure if you
have overloaded the UPS's outlets, see "OVERLOAD" LED description in the
"Basic Operation" Section.
Turn the UPS OFF.
3
Press and hold the "OFF" button
the unit to "Standby" mode. Release the button. The UPS output
will be OFF.
Voltage Selection
Your UPS system features an "Output Selection" mode that
allows you to select the voltage once the UPS is turned on.
NOTE: Your UPS system's default setting is 120V.
To select voltage: In AC mode, press and hold both "ON"
and "OFF/STANDBY"
Selection" mode. Press "ON" button to select output voltage
from 110 (40% LED flashing), 120 (60% LED flashing) or 127V
(80% LED flashing). After selecting voltage, press and hold
"OFF/STANDBY" button to exit.
WARNING! Make sure to plug your equipment into the UPS
before you select the voltage.
201112106 93-2729.indb 7
A
for one second. This will set
B
buttons to put the UPS in "Output
1
2
3
B
A
7
A
12/28/2011 3:44:05 PM