Maintenance (continued)
Assembly after maintenance
Bearing in mind the following points, assemble the parts following
the sequence for their removal in reverse.
l Arrange the Lossnay core with the air filter side downward.
l Filter have front and back side. Set the correct side of the filter
according to the arrow on the filter frame.
Specifications
Running current
Model name
LGH-150RVXT-E
LGH-200RVXT-E
LGH-250RVXT-E
* The above values apply during Lossnay ventilation when the fan speed is set to Fan speed 4 at the rating pressure loss and 230 V / 50 Hz.
* For the specifications at the other frequency or voltages, contact your dealer.
* The values given in the table for the noise level reflect the levels measured at a position 1.5 meters immediately below the unit in an anechoic chamber.
* Noise change or increase may occur because of the Bypass-Automatic function or Automatic fan speed change by timer setting and/or other
functions.
* Temperature Exchange efficiency (%) are based on winter condition.
* Mitsubishi Electric measures products according to Japan Industrial Standard (JIS B 8628), therefore P-Q curves are measured by chamber method.
* On-site commissioning measurements by pitot tube method could be as much 20% difference from JIS test room conditions. If the measuring
point is close to sources of turbulence like bends, contractions and dampers etc, it is difficult to measure air volume correctly. A straight duct
length more than 10D (D=duct diameter or equivalent) from the source of turbulence is recommended for correct measurement. On-site
measurement should therefore be measured in accordance with BSRIA guideline (Commissioning Air System. Application procedures for
buildings AG3/89.3(2001))
Maintenance and lifetime
The parts listed below are service parts. It is necessary that the regular check and the regular replacement or the replacement when it is broken.
In addition, expenses for parts and replacement work is charged to customers.
- Motor
- Printed circuit board
- Lossnay core (Around 10 years with maintenance at stated periods.)
- Air filter (Around 5 years with maintenance at stated periods)
After-sales servicing
Consult with your dealer about the after-sales services provided for
this Lossnay product.
Inspect your unit of good service!
Attentive inspection
Have you
noticed?
Eng-4
Air volume
Input power
(A)
(W)
(m
/h) (L/S)
3
4.3
792
1500
5.4
1000
2000
7.6
1446
2500
● Fan do not run when the unit is turned on.
● Abnormal noises or vibrations while the unit is running.
● Retarded or irregular rotations.
(Motors are component which requires maintenance.)
● Burnt odor.
● Corroded or damaged installation section.
l Note the difference of filter height between outdoor air filter and
return air filter.
Air filter for OA
Note:
l If
are indicated on the remote controller, turn off the
indication, after maintenance.
Static pressure
Supply
Exhaust
Temperature
(Pa)
(Pa)
417
175
100
556
175
100
694
175
100
If you hear strange sounds, if no air is blown out or if some other
trouble occurs, switch off the power and contact your dealer. Consult
with your dealer concerning the cost of inspection or repair work.
Air filter for RA
Exchange efficiency (%)
Enthalpy
Heating Cooling
80
70
69
80
72.5
70
77
68
65.5
Turn off the unit. Then,
contact your dealer for
Stop
prevention of failure or
running.
hazard. The dealer should
appraise the possible cost.
Unit: mm
Noise
Weight
(dB)
(kg)
39.5
156
39.5
159
43.0
198