Alarm 1 Action Type
a. 1 .a.t.
Defines alarm action type on operating cycle
(No Action). Changes only output related to the alarm. > Default.
no.ac.
(End Cycle Signal). Cycle ends (STOP) with acoustic and visual
e.cY.s.
signalling. Changes output related to the alarm, buzzer sounds and
on display fl ashes AL. 1 , until pressing OK.
(Audible Signal), Only acoustic signalling: buzzer sounds.
au.si.

10.2 2nd level parameters (for expert operators)

40
Conversion Filter
c.fLt.
Adc filter: number of means on analogue-digital conversions.
1...15 samplings. > Default: 10.
41
Starting Setpoint
s.spu.
Enables cycle starting setpoint to guarantee the programmed gradient for
the first step.
(Disabled) Cycle starting setpoint disabled.
dis.
(Enabled) Cycle starting setpoint selectable by the user.
En.
En.a.t. (Enabled Ambient Temperature) Fixed cycle starting setpoint
(25°C). > Default.
42
Chronometer
cHro.
Enables chronometer: with cycle in execution it shows the time elapsed from
cycle start; with cycle in STOP it visualizes the duration of the last cycle. At
switch-off it is reset to zero.
(Disabled) > Default
dis.
(Enabled)
En.
43
Power Consumption
pow.c.
This parameter defines the power of the heating group controlled by the device.
If the value selected is different from 0.0, pressing STEP (when no cycle is in
execution), it is possible to visualize the employed power consumption (Kwatt/
hour) of the last cycle. At switch-off value is lost.
0.0...999.9 KWatt/h. > Default 0.0.
24 - ATR902 - User manual