Descargar Imprimir esta página

Programming Of The Step (Segment); Programming Of The Alarm/Auxiliary (If Configured); End Programming - Pixsys ATR 902 Manual Instalador

Ocultar thumbs Ver también para ATR 902:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7.1.2 Programming of the step (segment)

Press
Red display visualizes 01-t .
4
STEP
Green display shows step time.
Increases, decreases value on
green display.
5
N.B.:Each cycle is composed of
max. 18 programmable steps,
after those it skips automatically
to point 10.
Red display visualizes 01-S . Green
display shows the step setpoint
6
STEP
(temperature that has to be
reached within given time).

7.1.3 Programming of the alarm/auxiliary (if configured)

Press
Red display visualizes 01-A.
7
Green display shows A1-of or
STEP
A1-on .
8
9
Back to point 4.
STEP

7.1.4 End programming

Press
The controller backs to STOP
10
mode, saving the cycle. Red
STEP
display visualizes stop .
Display
Display
Display
Enter the step duration in
hours:minutes.
N.B.: Set --.-- for endless time or
end for cycle end (if not all steps
are used) and skip to point 10.
With
or
(temperature reached at step end).
If AL. 1 is not programmed as
auxiliary time ( a.o.r.s. ) skip to
point 10.
Select auxiliary output status
during the step: A1-on for active
output and A1-of for not active
output.
User manual - ATR902 - 13
Do
select the setpoint
Do
Do

Publicidad