Recommendations For Installing The Knx; Electric Connections - Gewiss Chorus GW 10 795 Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

INSTALLATION INSTRUCTIONS

Recommendations for installing the KNX

1. The length of the BUS line between the thermostat and the power supply must not
exceed 350 metres.
2. The length of the BUS line between the thermostat and the furthest KNX device to be
commanded must not exceed 700 metres.
3. To avoid unwanted signals and overvoltages, do not use ring circuits.
4. Keep a distance of at least 4 mm between the individually insulated cables of the BUS
line and those of the electricity line (figure C).
5. Do not damage the electrical continuity conductor of the shielding (figure D).
ATTENTION: the unused BUS signal cables, and the electrical continuity
conductor, must never touch any live elements or the earthing
conductor.
Figure B shows a diagram of the electrical connections.
1. Connect the red wire of the BUS cable to the red clamp (+) of the terminal, and the
black wire to the black clamp (-). Up to 4 BUS lines can be connected to the BUS
terminal (same coloured wires on the same terminal) (figure E).
2. Insulate the shield, the electrical continuity conductor, and the other white and yellow
wires of the BUS cable (if a 4 conductor BUS cable is being used), that are not
necessary (figure D).
3. Insert the BUS clamp in the pins of the device. The correct insertion direction is
determined by the fixing guides. Insulate the BUS terminal with the special cover, that
must be fixed to the device. The cover guarantees the minimum separation distance
of 4 mm between the power cables and the BUS cables (figure F).
4. Connect any inputs and the output contact to the screw terminals on the back of the
thermostat (figure A).

Electric connections

20

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Chorus gw 12 795Chorus gw 14 795

Tabla de contenido