Sinking And Sourcing - Allen-Bradley Rockwell MicroLogix 1000 Instrucciones Para La Instalación

Ocultar thumbs Ver también para Rockwell MicroLogix 1000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 83

Sinking and Sourcing

Any MicroLogix 1000 DC input can be configured as sinking or sourcing
depending on how the DC COM terminal is wired.
Mode:
Definition:
The input energizes when high-level voltage is applied to the
Sinking
input terminal (active high). Connect the power supply VDC (–)
to the corresponding DC COM terminal.
The input energizes when low-level voltage is applied to the input
Sourcing
terminal (active low). Connect the power supply VDC (+) to the
corresponding DC COM terminal.
Sinking and Sourcing Wiring Examples
1761-L32BWA (Wiring diagrams also apply to 1761-L10BWA, -L10BWB, -L16BWA,
-L16BWB, -L16BBB, -L20BWA-5A, -L20BWB-5A, -L32BWB, -L32BBB.)
Sinking Inputs
VDC (+) for Sourcing
VDC (+) for Sinking
VDC (–)
for Sinking
+ 24V –
DC
I/0
I/1
I/2
I/3
DC
I/4
I/5
COM
COM
DC OUT
Sourcing Inputs
VDC (–) for Sinking
VDC (–) for Sourcing
VDC (+)
for Sourcing
+ 24V –
DC
I/0
I/1
I/2
I/3
DC
I/4
I/5
COM
COM
DC OUT
Installation Instructions
MicroLogix 1000 Programmable
Controllers
Sourcing Inputs
14–30 VDC
I/6
I/7
I/8
I/9
I/10
I/11
I/12
I/13
I/14
I/15 I/16
Sinking Inputs
14–30 VDC
I/6
I/7
I/8
I/9
I/10
I/11
I/12
I/13
I/14
I/15 I/16
VDC (–) for Sourcing
I/17
I/18
I/19
VDC (+)
for Sinking
I/17
I/18
I/19
13

Publicidad

Tabla de contenido
loading

Tabla de contenido