Installation Instructions
MicroLogix 1000 Programmable
Controllers

Using Mounting Screws

To install your controller using mounting screws:
1. Remove the mounting template
from the front of this document.
2. Secure the template to the mounting
surface. (Make sure your controller
is spaced properly.)
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the controller.
6. Leave the protective wrap attached
until you are finished wiring the
controller.

Mounting Your Controller Vertically

Your controller can also be mounted vertically within an enclosure using mounting
screws or a DIN rail. To insure the stability of your controller, we recommend
using mounting screws. For additional information, refer to the previous section.
To insure the controller's reliability, the following environmental specifications
must not be exceeded.
Top
A
Description:
Operating
Temperature
Side
Side
Operating Shock
(Panel mounted)
A
A
Operating Shock
(DIN rail mounted)
Bottom
DC input voltage derated linearly from +30 C (30V to 26.4V).
A
A. Greater than or equal
to 50.8 mm (2 in.).
Note: When mounting your controller vertically, the nameplate should be facing
downward.
6
Mounting
Template
Protective
Wrap
20145
Specification:
0 C to +40 C (+32 F to +113 F)
9.0g peak acceleration (11 1 ms duration)
3 times each direction, each axis
7.0g peak acceleration (11 1 ms duration)
3 times each direction, each axis