4
MAINTENANCE
Properly installed meters with sound connections and secure conduit fittings should
not require user maintenance. If the meter is functioning abnormally, consult the FAQ /
Troubleshooting guide. If the answer cannot be found there, contact Leviton technical support.
5
TROUBLESHOOTING / FAQ
Problem
1. LCD Display not on
2. Load LED not flashing
3. Registered consumption low
4. Reverse phase LED illuminated
Solution
•
Check to make sure all connections are wired
•
Test the voltage being supplied to the meter
using an AC voltmeter
•
With power off, remove any additional in-line
fuses and test the circuit with the appropriate test
equipment
•
Verify CT connections and orientations
•
Make sure there is sufficient load to draw a
significant current
•
Test the voltage being supplied to the meter
using an AC voltmeter
•
Check to make sure the reverse phase LED is
not on
•
Even if the reverse phase light is off, double-
check CT orientations. One CT installed in the
incorrect direction doesn't always illuminate the
reverse phase LED
•
Make sure that current and voltage connections
are in phase
•
Check power connections and fuses
•
Verify orientation and connection of CT wires
•
Ensure that phasing is correct (CT1 on Line 1,
CT2 on Line 2)
•
Verify that a load drawing more than 1 Amp is
connected to the meter
22