MAINTENANCE

Properly installed meters with sound connections and secure conduit fittings should
not require user maintenance. If the meter is functioning abnormally, consult the FAQ /
Troubleshooting guide. If the answer cannot be found there, contact Leviton technical support.
5
TROUBLESHOOTING / FAQ
Problem
1. LCD Display not on
2. Load LED not flashing
3. Registered consumption low
4. Reverse phase LED illuminated
Solution
Check to make sure all connections are wired
Test the voltage being supplied to the meter
using an AC voltmeter
With power off, remove any additional in-line
fuses and test the circuit with the appropriate test
equipment
Verify CT connections and orientations
Make sure there is sufficient load to draw a
significant current
Test the voltage being supplied to the meter
using an AC voltmeter
Check to make sure the reverse phase LED is
not on
Even if the reverse phase light is off, double-
check CT orientations. One CT installed in the
incorrect direction doesn't always illuminate the
reverse phase LED
Make sure that current and voltage connections
are in phase
Check power connections and fuses
Verify orientation and connection of CT wires
Ensure that phasing is correct (CT1 on Line 1,
CT2 on Line 2)
Verify that a load drawing more than 1 Amp is
connected to the meter