Danfoss VLT Micro Drive FC 51 Guía Rápida página 14

Ocultar thumbs Ver también para VLT Micro Drive FC 51:
Tabla de contenido

Publicidad

Guía rápida
1
1
4-** Limits/Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
*[0] Clockwise si par. 1-00 está
ajustado a close loop control
[1] CounterClockwise
*[2] Both si par. 1-00 está ajustado
a lazo abierto
4-12 Motor Speed Low Limit [Hz]
0,0-400,0 Hz *0,0 Hz
4-14 Motor Speed High Limit [Hz]
0,1-400,0 Hz *65,0 Hz
4-16 Torque Limit Motor Mode
0-400 % *150 %
4-17 Torque Limit Generator
Mode
0-400 % *100 %
4-4* Adj. Warnings 2
4-40 Warning Frequency Low
0,00-valor de 4-41 Hz *0,0 Hz
4-41 Warning Freq. High
Valor de 4-40-400,0 Hz *400,00 Hz
4-5* Adj. Warnings
4-50 Warning Current Low
0,00-100,00 A *0,00 A
4-51 Warning Current High
0,0-100,00 A *100,00 A
4-54 Warning Reference Low
–4999,000, valor de 4-55
* –4999,000
4-55 Warning Reference High
Valor de 4-54-4999,000
*4999,000
4-56 Warning Feedback Low
–4999,000, valor de 4-57
* –4999,000
4-57 Warning Feedback High
Valor de 4-56-4999,000 *4999,000
4-58 Missing Motor Phase
Function
[0] Off
*[1] En
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0,0-400,0 Hz *0,0 Hz
4-63 Bypass Speed To [Hz]
0,0-400,0 Hz *0,0 Hz
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No function
[1] Reset
[2] Coast inverse
[3] Coast and reset inv.
[4] Quick stop inverse
[5] DC-brake inv.
[6] Stop inv
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[16-18] Preset ref bit 0-2
[19] Freeze reference
12
Guía rápida
5-10 Terminal 18 Digital Input
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Setup select bit 0
[28] Catch up
[29] Slow down
[34] Ramp bit 0
[60] Counter A (up)
[61] Counter A (down)
[62] Reset counter A
[63] Counter B (up)
[64] Counter B (down)
[65] ResetCounter B
5-11 Terminal 19 Digital Input
Consulte par. 5-10. * [10] Reversing
5-12 Terminal 27 Digital Input
Consulte par. 5-10. * [1] Reset
5-13 Terminal 29 Digital Input
Consulte par. 5-10. * [14] Jog
5-15 Terminal 33 Digital Input
Consulte par.5-10 * [16] Preset ref
bit 0
[26] Precise Stop Inverse
[27] Start, Precise Stop
[32] Pulse Input
5-3* Digital Outputs
5-34 On Delay, Terminal 42 Digital
Output
0,00-600,00 s * 0,01 s
5-35 Off Delay, Terminal 42 Digital
Output
0,00-600,00 s * 0,01 s
5-4* Relays
5-40 Function Relay
*[0] No operation
[1] Control ready
[2] Drive ready
[3] Drive ready, Remote
[4] Enable / No warning
[5] Drive running
[6] Running / No warning
[7] Run in range / No warning
[8] Run on ref / No warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[16] Below frequency, low
[17] Above frequency, high
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[22] Ready, No thermal warning
[23] Remote ready, No thermal
warning
[24] Ready, Voltage ok
[25] Reverse
[26] Bus ok
[28] Brake,NoWarn
[29] Brake ready/NoFault
[30] BrakeFault (IGBT)
[32] Mech.brake control
[36] Control word bit 11
[41] Below reference, low
[42] Above reference, high
[51] Local ref. active
Danfoss A/S © Rev. 2014-02-27 Reservados todos los derechos.
5-40 Function Relay
[52] Remote ref. active
[53] No alarm
[54] Start cmd active
[55] Running reverse
[56] Drive in hand mode
[57] Drive in auto mode
[60-63] Comparator 0-3
[70-73] Logic rule 0-3
[81] SL digital output B
5-41 On Delay, Relay
0,00-600,00 s *0,01 s
5-42 Off Delay, Relay
0,00-600,00 s *0,01 s
5-5* Pulse Input
5-55 Terminal 33 Low Frequency
20-4999 Hz *20 Hz
5-56 Terminal 33 High Frequency
21-5000 Hz *5000 Hz
5-57 Term. 33 Low Ref./Feedb.
Value
-4999-4999 *0,000
5-58 Term. 33 High Ref./Feedb.
Value
–4999-4999 *50,000
6-** Analog In/Out
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
1-99 s *10 s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
0,00-9,99 V *0,07 V
6-11 Terminal 53 High Voltage
0,01-10,00 V *10,00 V
6-12 Terminal 53 Low Current
0,00-19,99 mA *0,14 mA
6-13 Terminal 53 High Current
0,01-20,00 mA *20,00 mA
6-14 Term. 53 Low Ref./Feedb.
Value
–4999-4999 *0,000
6-15 Term. 53 High Ref./Feedb.
Value
–4999-4999 *50,000
6-16 Terminal 53 Filter Time
Constant
0,01-10,00 s *0,01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2* Analog Input 2
6-22 Terminal 60 Low Current
0,00-19,99 mA *0,14 mA
6-23 Terminal 60 High Current
0,01-20,00 mA *20,00 mA
6-24 Term. 60 Low Ref./Feedb.
Value
–4999-4999 *0,000
6-25 Term. 60 High Ref./Feedb.
Value
–4999-4999 *50,00
6-26 Terminal 60 Filter Time
Constant
0,01-10,00 s *0,01 s
6-8* LCP Potentiometer
6-80 LCP Potmeter Enable
[0] Disabled
*[1] Enable
6-81 LCP potm. Low Reference
-4999-4999 *0,000
6-82 LCP potm. High Reference
-4999-4999 *50,00
6-9* Analog Output xx
6-90 Terminal 42 Mode
*[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[19] DC Link Voltage
[20] Bus Reference
6-92 Terminal 42 Digital Output
Consulte par. 5-40.
*[0] No Operation
[80] SL Digital Output A
6-93 Terminal 42 Output Min
Scale
0,00-200,0 % *0,00 %
6-94 Terminal 42 Output Max
Scale
0,00-200,0 % *100,0 %
7-** Controllers
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1
Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
MG02B905

Publicidad