Disposal
• To start one generator at a time the starter battery capacity has to be according
to the generator manual (minimum capacity: 60 Ah).
To start both generators at the same time you have to double the battery
capacity.
• The cross section of the battery connection cable for each generator has to be at
least:
– 10 mm² if the total length is less than 6 m
– 16 mm² if the total length is more than 6 m
I
NOTE
• The maximum distance between each generator to the junction box
is 15 m.
• The maximum length difference between the output cables of the
generators must be 2 m.
Proceed as follows (fig. k, page 14):
➤ Connect each generator to a junction box (1; not included in the scope of
delivery).
The minimum cross section for each generator output cable is 2.5 mm².
➤ Create a single output for the load (2) inside the junction box (1).
The minimum cross section for the parallel output cable is 6 mm².
➤ Connect the battery's negative pole to ground.
➤ Connect the output ground cable to ground.
➤ Connect the change over switch AG 113 (available as accessory) between the
junction box and the load.
➤ To properly run the generators in parallel connect the inverters (4) of each
genarator using the parallel cable (3; available as accessory).
11
Disposal
➤ Place the packaging material in the appropriate recycling waste bins wherever
possible.
M
If you wish to finally dispose of the product, ask your local recycling centre
or specialist dealer for details about how to do this in accordance with the
applicable disposal regulations.
32
TEC29 EV
EN

Publicidad

Tabla de contenido
loading

Tabla de contenido