11. WIRING DIAGRAM

12. ELECTRICAL CONNECTIONS

The electrical installation must be performed by a fully qualified electrician, and in accordance with local electrical
standards and the wiring diagram corresponding to the unit model.
Any modification performed without our prior authorisation may result in the unit's warranty being declared null
and void.
The power supply cable section must be sufficient to provide the appropriate voltage to the unit's power supply
terminals, both at start-up and under full load operating conditions.
The power supply cable shall be selected in accordance with the following criteria:
1. Power supply cable length.
2. Maximum unit starting current draw – the cables shall supply the appropriate voltage to the unit
terminals for starting.
3. Power supply cables' installation mode.
4. Cables' capacity to transport the total system current draw.
Short circuit protection shall be provided. This protection shall comprise fuses or circuit breakers with high breaking
capacity, mounted on the distribution board.
A device to disconnect all the power conductors with an approved minimum opening distance must
be included in the mains power supply according to best installation practices.
Before starting any electrical connection, check that the electrical supply corresponds to the specification indicated
on the unit's maker's plate. Each cassette in equipped with a terminal block located inside the cassette cabinet.
All the cassettes are intended to operate on a normal voltage of 230 V ± 10% / Single phase / 50Hz + Earth.
The wiring diagram affixed to the unit illustrates the connections to be made.
The manufacturer and their representatives decline all responsibility for any accidents caused by
inadequate or non-existent earthing of the installation.
If the local control includes an remote ambient temperature sensor and/or a set temperature adjustment module,
these shall be connected with shielded cable and shall not pass through the same conduits as the power supply
cables as the voltages induced may create reliability faults in the unit's operation.
SEE APPENDIX
Before carrying out any work on the equipment,
make sure that the electrical power supply is
disconnected and that there is no possibility
of the unit being started inadvertently.
Non-compliance with the above instructions
can lead to injury or death by electrocution.
THE UNIT MUST BE EARTHED.