13.2.2.6. TECHNICAL CHARACTERISTICS
Operating voltage
Contact configuration
Temperature range
Switching current at 230V AC
Switching differential
Sensor system
Switches
13.2.2.7. FINAL OPERATIONS
13.2.2.7.1. ADJUSTEMENT OF THE TEMPERATURE RANGE
The room thermostat is set in the factory for a minimum temperature of +5°C and a max. temperature of +30°C.
Two rings are provided inside the knob for reducing the temperature range.
²
Example: 12°C to 25°C.
13.2.2.7.2. ADJUSTEMENT PROCEDURE
1. Setting the temperature range
e.g. max. 25°C, min. 12°C.
2. Remove the control knob.
3. Use a pointed object to align the mark on the red ring (max. value) with the desired maximum
temperature (25°C), turning the red index opposite the outside numbers counterclockwise.
4. Use a pointed object to align the mark on the blue ring (min. value) with the desired minimum
temperature (12°C), turning the blue index opposite the inside numbers clockwise.
5. Install the control knob.
The temperature ranges can be graduated in:
²
degrees Celsius °C
from 5°C to 30°C
²
number 1 to 6
1=5°C
2=10°C
3=15°C
4=20°C
5=25°c
6=30°C
230V
50Hz
SPDT
5 to 30°C
6A (cos ϕ=1) / 3A (cos ϕ =0.6)
approx. 0.5 K
bimetal
ON / OFF
mode of operation
fan speed
16