Drill Wall Hole For Connective Piping - EAS ELECTRIC R32 Manual De Usuario

Ocultar thumbs Ver también para R32:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Step 4: Network address set (some models)
(Only unit of 18000Btu/h has the function that
Network address set.)
Every air-conditioner in network has only one
network address to distinguish each other.
Address code of air-conditioner in LAN is set by
code switches S1 & S2 on the Main Control Board
of the indoor unit, and the set range is 0-63.
Page 24
Step 5:

Drill wall hole for connective piping

1. Determine the location of the wall hole
based on the location of the outdoor unit.
2. Using a 65mm (2.5in) or 90mm(3.54in)
(depending on models )core drill, drill a
hole in the wall. Make sure that the hole
is drilled at a slight downward angle, so
that the outdoor end of the hole is lower
than the indoor end by about 12mm (0.5in).
This will ensure proper water drainage.
3. Place the protective wall cu in the hole. This
protects the edges of the hole and will help
seal it when you nish the installation process.
CAUTION
When drilling the wall hole, make sure to
avoid wires, plumbing, and other sensitive
Outdoor
≈ 12mm / 0.5 inch
Wall
Indoor
V.2

Hide quick links:

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

R290

Tabla de contenido