Elko EP HRN-33 Manual Del Usuario página 3

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-14/2017 Rev.: 1
Characteristics
• it serves to control supply voltage for appliances sensitive to supply tolerance,
protection of the device against under / over voltage
• HRN-3x is band voltage relay, HRN-6x is over / under voltage relay. For
diff erence - see graph of function.
• HRN-33, HRN-63
- monitors voltage in range AC 48 - 276 V
- U max and U min can be monitored independently
• HRN-34, HRN-64
- like HRN-33, but voltage range is DC 6 - 30 V
- monitoring of battery circuits (24 V)
• HRN-35
- like HRN-33, but independent output relays for each voltage level
- switching of other loads possible
• HRN-37, HRN-67
- like HRN-33, monitors voltage in range AC 24 - 150 V
- it is possible to monitor level of overvoltage and undervoltage independently
• adjustable time delay for all types is 0 - 10 s (to eliminate short voltage drops
or peaks)
• voltage Umin adjusted as % of Umax
• 3-state indication - LEDs indicating normal state and 2 fault states
• supply from monitored voltage (monitors level of its own supply)
• 1-MODULE, DIN rail mounting
Description
HRN-35
HRN-37
1
2
3
3
4
4
5
5
6
6
6
1. Supply / monitoring
terminals
1
2. LED indication for relay
status
2
3. Adjusting of upper value
Umax
4. Adjusting of time delay
5. Adjusting of bottom value
Umin
6. Output contatcs
HRN-33
HRN-63
HRN-34
HRN-64
HRN-35
HRN-67
HRN-37
Monitoring voltage relay
Symbol
HRN-33,HRN-37, HRN-63, HRN-67
HRN-34, HRN-64
A1
16
18
< U
A2
15
Connection
HRN-33, HRN-37,
HRN-63, HRN-67
Un
A1
A2
15 16 18
Indication LED
HRN-33, HRN-37
Normal state
Umin<Un<Umax
green LED = ON,
red LED = OFF
Exceeded Umax (overvoltage)
Drop below Umin (undervoltage)
Un>Umax or Un<Umax
green LED = ON,
red LED = ON
HRN-63, HRN-67
Exceeded Umax (overvoltage)
Un>Umax
green LED = ON,
red LED = ON
Drop below Umin (undervoltage)
Un<Umin
green LED = ON,
red LED = OFF
HRN-35
Normal state
Umin<Un<Umax
green LED = ON,
red LED = OFF
Drop below Umin (undervoltage)
Un<Umin
green LED = OFF,
red LED = ON
1 / 2
HRN-35
A1
16
18
A1
< U
< U
A2
15
A2
HRN-34,
HRN-64
Un
-
+ +
A1
A2
15 16 18
HRN-34
Normal state
Umin<Un<Umax
green LED = ON,
red LED = OFF
Exceeded Umax (overvoltage)
Drop below Umin (undervoltage)
Un>Umax or Un<Umax
green LED = OFF,
red LED = ON
HRN-64
Exceeded Umax (overvoltage)
Un>Umax
green LED = OFF,
red LED = ON
Drop below Umin (undervoltage)
Un<Umin
green LED = ON,
red LED = OFF
Exceeded Umax (overvoltage)
Un>Umax
green LED = ON,
red LED = ON
EN
16 18
26 28
15
25
HRN-35
Un
A1
A2
25 26 28
15 16 18

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hrn-34Hrn-35Hrn-37Hrn-63Hrn-64Hrn-67

Tabla de contenido