Operation mode needs to be set to "OFF/RESET" to modify the variables. Some variables can be modified also using
different modes other than "OFF/RESET".
If you cannot change a variable in any condition, this is shown as follows:<400>
showing that the parameter cannot be changed in this status.
To exit the programming menu, use the EXIT/SHIFT
How to input string value
3.4.1.3
For some parameters you will have to set a value for the string data.
In this case, the square brackets [ ] opening and closing the variable will blink after pressing ACK/ENTER
cursor will display under the first character of the string. Using the LEFT
the character to be changed. Use the vertical UP
selected character. Repeat the procedure for each character that needs changing.
Press the ACK/ENTER
Direct access to the previous page
3.4.1.4
You can directly open the last programming page displayed . This is possible if, when exiting programming mode,
instead of going back though the menus until you exit programming, you hold down EXIT/SHIFT
secondi.
It is also possible to obtain the same result entering programming mode after Gen-set automatically exited programming.
Gen-Set automatically exits programming mode either if no operation is performed in 60 seconds or the lockable selector
is switched to MAN or AUTO.
Alarms and protection parameters
3.4.1.5
Protections and alarms can generally be configured using dedicated variables. Generally, the trip time can also be
configured.
Setting the trip time to 0 disables the protection.
3.4.2
Status information (S.xx)
In this way, information on the system status is provided.
You can scroll through the various pages using the LEFT
Page S.01 displays information on the system status. Part of this information is displayed in the bottom status bar.
The alarms page (S.02) is displayed automatically in case of malfunction. This page also contains the diagnostic
information on motors with the J1939 or MTU interface.
- Bus
communication status.
Three possible messages:
- ERROR-ACTIVE: normal operation
- ERROR-PASSIVE: communication is working despite faults (errors).
- BUS-OFF: Gen-set interrupted the connection to the bus due to too many errors.
button.
(confirm) button or the EXIT
and RIGHT
and DOWN
Ref. 1a
Ref. 1a
(abort) button to end the procedure.
and RIGHT
buttons.
User's Manual HT GC310/HT GC350/HT GC500
and a
buttons, you can select
scroll buttons to modify the
per circa 2
13