Specification; Maintenance And Repair - Amprobe INSP-3 Manual De Uso

Comprobador de inspección de cableado
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

NOTE: A good quality 3 to 2 wire adapter may be
used to test ungrounded systems with little loss in
accuracy.
Lighting or motor circuits may be tested by using a
good quality plug to clip lead adapter having not
smaller than 14 gauge wire and not longer than
4 feet.
Large power disturbances or spikes may cause
erratic readings.

SPECIFICATION

Load: Constant 0, 10,15 or 20 AMP simulation
regardless of line voltage
Operating Voltage: 95-120V AC
Power: 9V Alkaline Battery
Fuse: ½ Amp, 125V. Not user replaceable.
GFI Trip: 6.0 mA nominal to trip GFI, 30 mA to trip RCD
AFCI Trip: Up to 8, 120 Amp pulses within ½ second
period
Operating Temperature: 32 °F to 120 °F (0 °C to 50 °C)
Accuracy: +/- 2%, +/- 2 digits.

MAINTENANCE AND REPAIR

If there appears to be a malfunction during the
operation of the meter, the following steps should be
performed in order to isolate the cause of the problem.
1. Check the battery. Replace the battery
immediately when the unit doesn't turn ON.
2. Make sure you use the power cord provided
with the unit
11

Publicidad

Tabla de contenido
loading

Tabla de contenido