Specifications

Ranges
Full Scale
1.9999 mΩ
19.999 mΩ
199.99 mΩ
1.9999 Ω
19.999 Ω
199.99 Ω
1999.9 Ω
Display
Measurement
Range and Safety
Measurement
Mode
Control
Speed
Test Method
Test Current Accuracy
Output Current Stability
18
Resolution
Accuracy
0.1 µΩ
±0.2% ±0.2 µΩ
1 µΩ
±0.2% ±2 µΩ
10 µΩ
±0.2% ±20 µΩ
100 µΩ
±0.2% ±0.2 mΩ
1 mΩ
±0.2% ±2 mΩ
10 mΩ
±0.2% ±20 mΩ
±0.2% ±0.2 Ω
100 mΩ
DLRO10
4
1
/
digit seven segment LED
2
LED Indication
Manual, Auto, Continuous, High Power
Fully Automatic
<3s for forward & reverse current and to display average
Single cycle reversing d.c. ratiometric measurements and average result calculated.
<100 ppm per second at higher currents
Full Scale Volts
Test Current
20 mV
20 mV
20 mV
20 mV
20 mV
20 mV
200 mV
Large backlit LCD
Manual, Auto, Continuous,
High Power, Unidirectional.
Fully Automatic with manual
override of maximum current
10%
<10 ppm per second @ 10 mA
10 A
1 A
100 mA
10 mA
1 mA
100 µA
100 µA
DLRO10X