Specifications
Maximum Lead Resistance
Voltmeter Input Impedance
Hum Rejection
Data
Transfer
Storage
Memo Field
Battery
Capacity
Life
Recharge
Charging Time
Temperature
Operation
Storage
Calibration
Coefficient
Standard charging
Fast charging
Humidity
Max
Altitude
Max
Safety
EMC
Dimensions
Weight
DLRO10
100 mΩ total for 10A operation irrespective of battery condition.
> 200 kΩ
Less than 1% ± 20 digits additional error
with 100 mV peak 50/60 Hz. on the potential leads.
Warning will show if hum or noise exceeds this level.
7 Ah NiMH rechargeable.
Typically 1000 x 10 A tests before recharge
Via External 90V - 260 V 50/60 Hz charger or from 12 to 15 V d.c. supply
2.5 hours to 90% capacity, 4 hrs for full charge
+5°C to +45°C (41°F to 113°F) at full specification.
-10°C to +50°C (14°F to 122°F) at reduced acuracy
-20°C to +70°C (-4°F to 158°F)
20°C (68°F)
<0.01% per oC from 5°C to 40°C (<0.006% per °F from 41°F to 104°F)
0°C to +45°C (32°F to 113°F)
+10°C to +45°C (50°F to 113°F)
90% RH @ 40°C (104°F) non-condensing
2000m (6562 ft.) to full safety specifications
In accordance with EN61010-1 600 V Category III
In accordance with EN50081-1 and EN50082-1 (1992)
220 x 100 x 237 mm (8.6 x 4 x 9.5 in)
2.6 kg (5
3
/
lb.) including battery module
4
DLRO10X
Real Time or from storage via RS232
700 tests
Up to 200 characters per test via
integral alphanumeric keypad.
19