6.3.3 Mode of loading/replenishing of the stove
system fluid (Fig. 6.4)
Before performing the operations
listed below, be sure to have connected
both the delivery and return pipes (see
par. 6.3.2).
The options are as follows:
1) Connect a water pipe coming from
the water mains to the filling tap L,
open the vent valve B (Fig. 6.3.1), open
the filling valve M, making the water
flow until the stove is completely filled.
Close the vent valve and wait for the
minimum operating pressure (1 bar)
to be reached, which can be checked
from the pressure gauge on the stove.
2) Connect a water pipe coming from
the water mains to the system drain
J, open the vent valve, open the
drain valve K, making the water flow
until the stove is completely filled.
Close the vent valve and wait for the
minimum operating pressure (1 bar)
to be reached, which can be checked
from the pressure gauge on the stove.
3) I f t h e d o m e s t i c s y s t e m i s
equipped with manual or automatic
replenishment, the stove can be filled
through the delivery and return pipes.
T h e n o p e n t h e v e n t v a l v e B
(Fig. 6.3.1), open the bypass valve
on the anti-condensation valve N,
making the water flow from the system
until the stove is completely filled.
Close the vent valve and wait for the
minimum operating pressure (1 bar)
to be reached, which can be checked
Fig. 6.4a
from the pressure gauge on the stove.
Close the bypass valve in the anti-
condensation valve (Fig. 6.4a).
004778021 - 10/01/2020 - PN - Italy