Genius Brain 03 Instrucciones Para El Uso página 22

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 37
Pagina 
BRAIN 03 / BRAIN 04
Guide for the installer
The control unit has a handy display for viewing and programming the operating parameters.
The display shows gate status during normal operation. The displayed values are indicated on the following table:
DISPLAYED
VALUE
- -
Gate at rest
O P
Gate opening or opened
t c
Gate open in pause status (Only with automatic re-closure enabled)
C L
Gate closing
The operating parameters of the control unit are identified by two characters, one letter, lower case or upper case, and the
number. The letter identifies the parameter we are modifying, and the number the set value. For example, if "A2" appears on
the display, this means that we are modifying the power of the motor and the sensitivity of the electronic clutch, letter A, which
is currently on value 2.
Before you begin adjusting the operating parameters, select the type of operation for the control unit: with or without
encoder (see paragraph 6)and any extra travelling distance.
To access operating parameter adjustment, follow the instructions below:
1.
When you have made all the necessary connections, power up the system and check if all the signalling LEDs are in the
situation specified in paragraph 8.
2.
The display shows value "--".
3.
Press and hold down push-button P2 until the display shows the name and value of the first parameter.
4.
Press push-button P1 to change the value of the parameter.
To move on to the next parameter, press push-button P2.
5.
6.
When 60 seconds have elapsed without any key being touched, the control unit exits the adjustment mode. You can
manually exit the adjustment mode by scrolling all the parameters with push-button P2. When the displays shows value
"--", you have returned to normal operation.
The following table summarises all settable parameters and the assignable values.
DISPLAY
Adjustment of sensitivity of the electronic clutch and of motor power.
A1
Minimum motor power, more sensitive to obstacle
A2
Medium-low motor power, medium-high sensitivity to obstacles
A3
Medium-high motor power, medium-low sensitivity to obstacles
A4
High motor power, low sensitivity to obstacles
Leaf 2 delay: this parameter enables you to select the de-synchronisation time of the two leaves.
b1
0.5 seconds
b2
5 seconds
b3
10 seconds
b4
20 seconds
Automatic Reclosure: this function enables or disables automatic gate reclosing
c0
Disabled
c1
Enabled
Operation of OPEN A command: this function determines the behaviour of the OPEN A (total opening) push-button.
d0
Opens / Closes / Opens
d1
Opens / Stops / Closes / Stops
Condominium function: if this function is enabled while the gate is being opened, the start command is disabled.
E0
Disabled
E1
Enabled
9. OPERATION OF DISPLAY
10. ADJUSTING THE OPERATING PARAMETERS
DESCRIPTION
GATE STATUS

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Brain 04

Tabla de contenido