1.4 Unit Lifting
Hanger brackets at 4 corner of the unit are
used for unit lifting purpose.
The angle A of the chain should be at least 45°,
and insulation should be added at 4 corner of
the chain to prevent the damage of the panel
when lifting.
1.5 Drain piping
•
A 1 FPT condensate drain fitting is provided. The drain pipe can
be led out at the front side.
•
The drain pipe must be provided with a trap on the outside of
the unit and also installed at an incline for proper drainage, as
shown in the right.
•
To prevent condensate formation and leakage, provide the drain
pipe with insulation to safeguard against sweating.
•
Upon completion of the piping work, check that there is no
leakage and that the water drains off properly.
The drain piping should have a drain trap.
A 70mm
B 2C
C 2X ESP
Drain trap
Note: ESP = External Static Pressure
Drain trap for condensate
INSTALLATION OF THE UNIT
UAT(Y)(P)60~200A
Drain piping
The drain pipe
should extend
below this level.
3
UAT(Y)(P)250, 300A
Hanger Bracket
Spreader Bar
Chain
Lifting Holes for shackle
(4 corners)
UAT(Y)(P)360, 420A
Chain
Lifting Beam