Annex 1: Configuring the CPU
1.
Get "Online" with the PLC via the "Login" command on the "Online" menu.
2.
Go to the "PLC-Browser" option on the "Resources" tab.
3.
Activate the IPSSET command in the command line with the desired configuration addresses, always
respecting the syntax.
Respect the command syntax and spaces between fields. The syntax is the following:
IPSET < ETH_0 "IPaddress" "subnetmask" "Gatewayaddress" > < ETH_1 "IPaddress"
"Subnetmask" "Gatewayaddress" >
The fields "IPaddress", "subnetmask" and "Gatewayaddress" are made up of 4 numeric fields
separated by points. For example:
IPSET < ETH_0 90.0.8.63 255.255.255.0 0.0.0.0 > < ETH_1 90.0.8.64 255.255.255.0 0.0.0.0 >
Upon making a change in IP, the PLC automatically restarts.
Once reset, the PLC starts with the new configuration.
4.
With the IPGET command in the command line you see the configuration available on the PLC.
ABP2011IQM01_ - Installation and Operation Manual