D-Link DGS-6600 Serie Guía De Instalación Rápida página 6

Ocultar thumbs Ver también para DGS-6600 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

equipment frame. Use screws to fasten
them to the bracket of the cabinet/ Once
fastened, the equipment should be stable
and immobile.
Installing the Fan Tray
The DGS-6600-FAN fan tray is used as the
DGS-6604's ventilation system. Carry out the
following to install the fan tray:
1. Use the thumb-screws to remove the fan
tray blank panel.
2. Insert the fan tray into the guide rail of the
fan tray slot.
3. Secure the fan tray by tightening the fan
tray's captive-screws.
Figure 4. Installing the Fan Tray
Installing the Power Supply(s)
The DGS-6604 switch is powered up using an
AC power supply. The procedure for installing
the AC power supply is shown in the diagram
below:
Figure 5. Installing the Power Supply
6 u D-Link DGS-6604 Modular Switch
Connecting the System Ground
A working ground GND is installed on the back
of DGS-6604. GND should be directly con-
nected to the ground bar of the equipment
room. If a digital grounding bar and an analog
grounding bar exist in the equipment room, the
GND should be connected to the digital bar.
Ground Connection
Figure 6. Ground Connections on the back of the
DGS-6604
Precautions.
The sectional area of the grounding cable
(min. of 18AWG) should be selected to safely
conduct the maximum possible current. Use
insulated cables of good conductivity.
Do not use bare wire.
The grounding resistance for combined
grounding should be less than 1 Ohm (Ω).
Simple Grounding Steps
Unfasten the nut on the rear grounding
post of the equipment.
Affix the terminal of the grounding cable to
the grounding pole.
Fasten the nut back on the grounding post.
Connect the other end of the grounding
cable to a suitable grounding bar.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dgs-6604

Tabla de contenido