SPECIFICATIONS
ELECTRICAL RATINGS:
Input Voltage: 18 to 30 VAC, 60 Hz
Current: 0.2 amp + MV @ 25
Relay Contact Ratings:
Main Valve Relay: 1.5 amp @ 25 VAC 60 Hz
Spark Output:
Gap: 0.1" - 0.2", 15kV 25Hz
Max cable length: 3ft (0.9m)
Flame Current Requirements:
Minimum current to insure flame detection: 2 µA DC*
Maximum current for non-detection: 0.2 µA DC
Maximum allowable leakage resistance: 100 M ohms
* Measured with a DC microammeter in series with the
flame probe lead
OPERATING TEMPERATURE RANGE:
-40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
To 95% relative humidity (non-condensing)
MOUNTING:
Surface mount or 4" x 4" junction box
GASES APPROVED: Natural, Manufactured, Mixed,
Liquid Petroleum, and LP Gas Air Mixtures.
INSTALLATION
MOUNTING AND WIRING
WARNING
!
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could
cause shock or fire hazard.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete. Failure to earth ground the appliance
or reversing the neutral and hot wire connection
to the line can cause shock hazard.
Shut off main gas to heating system until
installation is complete.
Route and secure all wiring as far from flame as
practical to prevent fire and/or equipment damage.
2
C
O
Program Key Timing Specifications Quick Reference
Timing and Retry
PROGRAM
TRIAL
KEY
FOR
(COLOR)
IGNITION
A (blue)
4 Sec.
B (red)
4 Sec.
C (green)
7 Sec.
D (violet)
7 Sec.
E (orange)
7 Sec.
F (yellow)
7 Sec.
G (blue\red)
11 Sec.
H (red\green)
11 Sec.
Program
Key
Fig. 1 – Program Key installation
NOTE
Replace control as unit – no user serviceable parts.
All wiring should be installed according to local and national
electrical codes and ordinances.
The control may be mounted in any orientation on a
convenient surface using two #6 x 5/8" sheet metal screws.
If desired, control can be mounted on a 4" x 4" junction
box using two #8-32 x 5/8" machine screws. The control
must be secured to an area that will experience a minimum
of vibration and remain below the maximum ambient
temperature rating of 175°F. The control is approved for
minimum ambient temperatures of –40°.
Refer to the wiring diagrams and wiring table when
connecting the control to other components of the system.
UL approved 105°C rated 18 gauge minimum wire is
recommended for all low voltage connections. UL approved
105°C rated 16 gauge minimum wire is recommended for all
line voltage connections.
After installation or replacement, follow appliance
manufacturer's recommended installation/service instructions
to insure proper operation.
PRE-
INTER
RETRIES
PURGE
PURGE
2
0 Sec.
90 Sec.
2
30 Sec.
90 Sec.
2
0 Sec.
90 Sec.
2
30 Sec.
90 Sec.
0
0 Sec.
N/A
0
30 Sec.
N/A
0
0 Sec.
N/A
0
30 Sec.
N/A