Descargar Imprimir esta página

Emerson White-Rodgers 50D50-842 Instrucciones De Instalación página 3

Publicidad

INSTALLATION
MV
Gas
(GND)
Valve
THERMOSTAT OR
ALTERNATE
CONTROLLER
Fig. 2 – Typical hookup for White-Rodgers replacement
with separate flame sense and spark probes
NOTE: Max length of spark cable should be less than 3ft (0.9m) and rated at 15kV. The cable must not run in
continuous contact with any metal surface or spark voltage is greatly reduced. Use ceramic or plastic standoff
insulators as required. Ensure burner is grounded directly to module for spark return path.
INSTALL PROGRAM KEY
The control replaces all listed models with the following features:
• direct spark ignition
• remote rod flame sense or direct flame sense through ignitor
• one or three ignition tries
• four to eleven second trial for ignition time
• pre-purge options zero or 30 seconds
Eight program keys are provided for different applications. Timings and Retries for each program key are shown in the Speci-
fications section on page 2 of this installation manual. Choose the proper program key for the application. Install the selected
program key in the slot on the left side of the module (see figure 1) and fit the timing label on the cover.
If the module you are replacing is not listed in the table contact the manufacturer of the appliance for a recommended replace-
ment or retrofit.
After inserting the proper program key, dispose of the remaining keys to ensure the correct key remains in the module.
If control fails to operate see troubleshooting guide for remedy.
MANUFACTURER
Honeywell
Honeywell
Honeywell
Honeywell
Honeywell
Honeywell
Honeywell
Honeywell
Robertshaw
White-Rodgers
White-Rodgers
White-Rodgers
White-Rodgers
White-Rodgers
White-Rodgers
White-Rodgers
White-Rodgers
White-Rodgers
SPARK
PROBE
FLAME
FLAME
PROBE
Burner Ground
LIMIT
CONTROLLER
(GND)
TRANSFORMER
LIMIT
TABLE 2. Cross Reference for Program Key and Wiring Instruction
MODEL
S8680 (generic)
S87B1008
S87B1016
S87C1006
S87C1014
S87D1004
S87D1012
S87J1026
DS845 780-504
50D20-50
50D20-51
50D20-52
50D20-150
50D20-152
50D20-160
50D20-162
50D21-1
50D21-60
MV
Gas
(GND)
Valve
L1 (HOT)
L2
THERMOSTAT OR
CONTROLLER
Fig. 3 – Typical hookup for White-Rodgers
replacement with direct flame sense through
single spark/sense probe
KEY
Various
C (green)
G (blue\red)
C (green)
G (blue\red)
C (green)
G (blue\red)
H (red\green)
C (green)
A (blue)
A (blue)
A (blue)
C (green)
C (green)
D(violet)
D(violet)
A (blue)
D(violet)
SPARK
JUMPER
PROBE
LINK
FLAME
Burner Ground
LIMIT
CONTROLLER
(GND)
TRANSFORMER
ALTERNATE
LIMIT
WIRING
Fig 2 / 3
Fig 3
Fig 3
Fig 2
Fig 2
Fig 2
Fig 2
Fig 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
Fig 2 / 3
L1 (HOT)
L2
3

Publicidad

loading

Este manual también es adecuado para:

White-rodgers rescue 50d50-842