Lamborghini Caloreclima ECO 3 Manual Para La Installación Y El Mentenimiento página 35

Quemadores para gasóleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Standby, other intermediate states
Fuel preheating "on", waiting time 5s.max
Ignition stage
Correct operation
Incorrect operation, current level of
flame detector below permitted minimum
Drop in voltage
Burner lock out
Fault
Stray light before burner ignition
Rapid flashing for diagnostics
If the burner is locked out, there will be a steady red light on the lock out pushbutton.
By pressing the transparent pushbutton, the control and checking device will be released.
By pressing it for more than 3 seconds, the diagnosis stage will be activated (red light flashes
rapidly). The table below describes the causes of the lock out or fault in relation to the number
of flashes (always red). The diagnosis function is interrupted by pressing the release button for
at least 3 seconds..
DIAGNOSIS OF LMO EQUIPMENT FAULTS AND LOCK OUT
Visual indication
2 flashes
¬¬
3 flashes
¬¬¬
4 flashes
¬¬¬¬
5 flashes
¬¬¬¬¬
6 flashes
¬¬¬¬¬¬
7 flashes
¬¬¬¬¬¬¬
8 flashes
¬¬¬¬¬¬¬¬
9 flashes
¬¬¬¬¬¬¬¬¬
10 flashes
¬¬¬¬¬¬¬¬¬¬
EQUIPMENT STATE INDICATORS
Description
Condition
List operating anomalies
Possible causes
No flame signal
- Faulty fuel valves
- Faulty flame detector
- Incorrect burner setting, no fuel
- No ignition
Not used
Stray light on ignition
Not used
Not used
No flame signal during operation
- Faulty fuel valves
- Faulty flame detector
- Incorrect burner setting, no fuel
Anomalies in fuel preheating time
Not used
Incorrect electrical connection or damage to equipment
Colour sequence
No light
Yellow
Yellow, flashing
Green
Green, flashing
Alternating yellow red
Red
Red, flashing
Alternating green, red
Red, rapid flashing
UK
35

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido