2.3 Features

ETL LISTED Certified to CSA C22.2 No 61010-1, Conforms to UL Std. 61010-1, UL Std. 2075
Low-level meter capable of displaying from 0-200 ppm of CO
The CM-xx meets the Uniform Building Code for enclosed garages and meets OSHA standards for CO exposure
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
CM-xx mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
Calibration kit is available. One screw allows access for calibration or gas test
Where required by federal, state, local regulations or the Authority Having Jurisdiction, CM-6 and CM-12 are required to be used with Listed
1
Horn/Strobe model 78-2900-0211-X* to meet the 85dB(A) Audibility requirements of Standards UL 2075.
*Where "X" represents lens cover color, R for red lens cover, G for green lens cover, B for blue lens cover, O for amber lens cover, C for clear lens cover.

2.4 Specifications

Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Color: White or Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation: selectable at diS (disable), 15 ppm, 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. (default) or N.C.
Alarm relay settings: diS, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default)
Current Loop, 4-20 mA for 0-200 ppm CO, selectable to 'bAS' (default), 'EnH', OFF
Calibration Period Settings: dis(default), 3, 6, 12 and 24 (months)
Buzzer: 85 dBA at 10cm settable to off (default) or on
Digital display: 3-digit LED selectable to off (default) or on.
Operating Environment: 0°F to 125° F (-18

2.4.1 6-Series Low Voltage

Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA standby

2.4.2 12-Series Line Voltage

Power: 100-240VAC (50 TO 60 HZ)
Current: 1.0 A MAX
REV – 1.1
o
o
C to 52
C),10 to 90% RH non-condensing
[34-2900-0511-6]
1
6 |
P a g e